1. Introdução
This manual provides essential instructions for the installation, operation, maintenance, and troubleshooting of your APC Smart-UPS SRT 3000VA RM 230V (SRT3000RMXLI). This Uninterruptible Power Supply (UPS) is designed to provide high-density, true double-conversion online power protection for critical electronic equipment, including servers, voice/data networks, medical labs, and light industrial applications. Please read this manual thoroughly before installing or operating the UPS to ensure proper and safe usage.
2. Informações de segurança
Observe all warnings and operating instructions in this manual. Failure to do so may result in injury or equipment damage. This UPS contains hazardous voltagAtenção: Não tente desmontar a unidade. Não há peças que possam ser reparadas pelo usuário em seu interior.
Segurança Geral
- Este no-break é destinado somente para uso interno.
- Não opere este no-break sob luz solar direta, em contato com fluidos ou onde haja excesso de poeira ou umidade.
- Ensure the ventilation openings on the UPS are not blocked. Maintain adequate clearance around the unit for proper airflow.
- Connect the UPS power cable directly to a grounded wall outlet. Do not use extension cords or surge suppressors.
Segurança da bateria
- Batteries are heavy. Remove the battery module before installing the UPS in a rack or tower configuration.
- Battery service should be performed or supervised by personnel knowledgeable of batteries and the required precautions.
- Não descarte as baterias no fogo. As baterias podem explodir.
- Não abra ou mutile as baterias. O eletrólito liberado é prejudicial à pele e aos olhos. Pode ser tóxico.
- Substitua as baterias por baterias do mesmo tipo e quantidade que as instaladas originalmente.
3. Conteúdo da embalagem
Desembale cuidadosamente a unidade e verifique se há danos causados pelo transporte. Caso encontre algum dano, notifique a transportadora e o revendedor. A embalagem deve conter os seguintes itens:
- APC Smart-UPS SRT 3000VA RM 230V (SRT3000RMXLI) unit
- Battery module (may be pre-installed or separate)
- Rack-mounting hardware (rails, brackets)
- Tower stand (for tower configuration)
- Cabo de comunicação USB
- Cabo de comunicação serial
- CD de documentação
- Safety information and warranty guide
4. Produto acabadoview
The APC Smart-UPS SRT 3000VA RM 230V is a high-performance Uninterruptible Power Supply designed to protect your critical equipment from power disturbances. It features a rack/tower convertible form factor for flexible deployment.

Figura 1: Frente view of the APC Smart-UPS SRT 3000VA RM 230V. This image displays the front panel with the LCD display, control buttons, and ventilation grilles.
Componentes-chave
- Front Panel LCD Display: Provides real-time status information, configuration options, and alarm notifications.
- Botões de controle: Used to navigate the LCD menu, power on/off the UPS, and perform self-tests.
- Módulo de bateria: Fornece energia de reserva durante o uso.tages. Hot-swappable for easy replacement.
- Conector de alimentação de entrada: Conecta o UPS à fonte de energia da concessionária.
- Output Receptacles (IEC 320): Provide protected power to connected equipment.
- Communication Ports (USB, Serial): For connecting to a computer or network management card for monitoring and control.
- Porta EPO (Desligamento de Emergência): Allows for remote emergency shutdown of the UPS.
5. Configuração
Follow these steps for initial setup of your UPS.
Etapa 1: escolha um local
- Place the UPS on a sturdy, level surface or install it in a standard 19-inch rack.
- Ensure the ambient temperature is between 0°C and 40°C (32°F and 104°F).
- Maintain at least 10 cm (4 inches) of clearance at the front and rear of the unit for proper ventilation.
Step 2: Install the Battery Module
If the battery module is not pre-installed, slide it into the battery bay until it clicks into place. Connect the battery cables as indicated by the labels.
Step 3: Connect to Utility Power
- Conecte o cabo de alimentação de entrada do UPS a uma tomada CA de 230 V aterrada.
- The UPS will perform a self-test and the LCD display will illuminate.
Etapa 4: Conecte o equipamento
- Connect your critical equipment (servers, network devices, etc.) to the output receptacles on the rear of the UPS.
- Ensure the total load does not exceed the UPS capacity (3000VA / 2700W).
Step 5: Connect Communication Cables (Optional)
- Conecte o cabo USB ou serial do UPS ao seu computador ou servidor para monitoramento e desligamento seguro.
- Install the PowerChute software (available from APC website) on your computer for advanced management.
6. Operando o UPS
Ligando o UPS
Press and hold the power button on the front panel until you hear a beep. The UPS will start up and provide power to connected equipment.
Desligando o UPS
Press and hold the power button until the UPS shuts down. Ensure all connected equipment is safely shut down before powering off the UPS.
Visor LCD e navegação
The LCD display provides detailed information about the UPS status, battery charge, load level, and various settings. Use the navigation buttons (up, down, enter, escape) to browse through the menus and adjust settings.
Autoteste
Regularly perform a self-test to ensure the UPS battery and internal components are functioning correctly. This can typically be initiated via the LCD menu or PowerChute software.
7. Manutenção
Substituição da bateria
The UPS batteries have a typical lifespan of 3-5 years. The UPS will indicate when the batteries need replacement. Refer to the safety information before attempting battery replacement. Use only APC-approved replacement battery modules (APCRBC152).
Limpeza
Limpe a parte externa do UPS com um pano macio e seco.amp cloth. Do not use solvents or abrasive cleaners. Ensure ventilation openings are free from dust and debris.
Considerações ambientais
Store the UPS in a cool, dry place when not in use. Avoid extreme temperatures and humidity, which can shorten battery life.
8. Solução De Problemas
This section provides solutions to common issues you may encounter with your UPS.
| Problema | Possível causa | Solução |
|---|---|---|
| O nobreak não liga. | No utility power; Battery not connected; UPS fault | Check power outlet; Ensure battery cables are connected; Contact APC support if fault persists. |
| O nobreak emite bipes continuamente. | Funcionando com bateria; Sobrecarga; Bateria fraca | Check utility power; Reduce connected load; Allow battery to recharge. |
| Bateria não carrega | Battery disconnected; Battery fault; Internal fault | Verify battery connection; Replace battery if faulty; Contact APC support. |
| O equipamento conectado perde energia | UPS overload; Battery depleted; UPS fault | Reduce load; Allow battery to recharge; Contact APC support. |
9. Especificações
Detailed technical specifications for the APC Smart-UPS SRT 3000VA RM 230V (SRT3000RMXLI).
| Recurso | Detalhe |
|---|---|
| Número do modelo | SRT3000RMXLI |
| Marca | APC |
| Capacidade | 3000 VA/2700 Watts |
| Vol de entradatage | 230 Volts |
| Volume de saídatage | 230 Volts |
| Fator de forma | Rack/Tower Convertible (2U) |
| Tipo de Bateria | Chumbo ácido |
| Typical Runtime (Full Load) | Aproximadamente 4 minutos |
| Número de saídas | 8 x IEC 320 C13, 2 x IEC 320 C19 |
| Portas de comunicação | USB, Serial (RJ45), SmartSlot |
| Dimensões (A x L x P) | 8.5 cm x 43.2 cm x 63.5 cm (3.35 pol x 17.0 pol x 25.0 pol) |
| Peso | 31.3 kg (69 libras) |
| Cor | Preto |
10. Garantia e Suporte
Informações de garantia
APC provides a standard warranty for this product. Please refer to the warranty card included in your package or visit the official APC webConsulte o site para obter os termos e condições detalhados da garantia específicos para a sua região. Guarde o comprovante de compra para eventuais solicitações de garantia.
Suporte Técnico
For technical assistance, troubleshooting beyond this manual, or to inquire about replacement parts, please contact APC customer support. Support contact information can typically be found on the APC website or in the documentation provided with your unit. When contacting support, please have your model number (SRT3000RMXLI) and serial number ready.