GEYA GPS6-VAK

GEYA GPS6-VAK Adjustable Over & Under Voltage Protection Device User Manual

Model: GPS6-VAK (2P-40A-220V)

1. Introdução

This manual provides detailed instructions for the installation, operation, and maintenance of the GEYA GPS6-VAK Adjustable Over & Under Voltage Protection Device. This device is designed to protect electrical equipment from damage caused by voltage fluctuations, offering real-time monitoring of voltage, current, and cumulative energy consumption (KWH).

2. Recursos do Produto

  • Visor digital inteligente: Clear LED display shows voltage, current, and fault status for quick and straightforward monitoring.
  • Advanced Over & Under Voltage Proteção: Equipped with factory default settings of 275V overvoltage and 175V undervoltage, ensuring device safety.
  • Parâmetros ajustáveis: Offers a factory default reset time of 30s, adjustable from 2 to 900s to suit specific needs. Overvoltage e subvol.tage thresholds are also adjustable.
  • Monitoramento atual: Displays real-time current values (1-80A).
  • Energy Consumption (KWH) Metering: Displays the cumulative value of electricity metering.
  • Compact Size & DIN Rail Mounting: Ultra-small size, easily integrates with 35mm DIN Rail mounting, simplifying installation and providing a secure connection.

3. Especificações

EspecificaçãoValor
Número do modeloGPS6 Voltage / Current Protector
Volume de fornecimento avaliadotageAC220V (L-N)
Frequência Nominal50/60Hz
Vol avaliadotage220V
Corrente operacional nominal40A, 63A, 80A (This model: 40A)
Tempo de reinicialização1-900s (factory default: 30s)
Sobrevoltage Faixa de configuraçãoAC130-300V (factory default: 275V)
Undervoltage Faixa de configuraçãoAC80-210V (factory default: 175V)
Volumetage Histerese5V
Volumetage Precisão<1%
Sobrevoltage atraso de viagem5s
Tipo de montagemDIN Rail Mount (35mm)
Tipo de conectorTerminais de parafuso
Material de contatoSilver or Copper
Tipo de contatoNormalmente aberto
Modo de operaçãoAutomático
CertificaçãoCE

Dimensões do produto

Diagram showing the dimensions of the GEYA GPS6-VAK device.

Image: Dimensions of the GPS6-VAK device, showing a width of 38mm and height of 86mm for the front view, and a depth of 67.5mm and width of 35mm for the side view.

4. How to Choose Your Device (GPS6-VA5 vs. GPS6-VAK)

GEYA offers two main models in this series: GPS6-VA5 and GPS6-VAK. The primary difference lies in their functionality. This manual specifically covers the GPS6-VAK model.

Comparison table between GEYA GPS6-VA5 and GPS6-VAK models.

Image: A comparison chart detailing features of GPS6-VA5 (Adjustable Voltage/Current Protector) and GPS6-VAK (Adjustable Voltage/Current Protector with KWH Measuring). Key differences include KWH measuring capability (present in VAK, absent in VA5) and rated frequency ranges.

  • GPS6-VA5: Vol. Ajustáveltage/Current Protector.
  • GPS6-VAK: Vol. Ajustáveltage/Current Protector with KWH Measuring. This model includes the ability to measure and display cumulative energy consumption (KWH).

5. Configuração e instalação

5.1 Montagem em trilho DIN

The GPS6-VAK device is designed for easy installation on a standard 35mm DIN rail. Ensure the rail is securely mounted in your electrical panel.

Image showing the GEYA device mounted on a 35mm DIN rail.

Image: The device is shown securely attached to a 35mm DIN rail, illustrating the ease of installation within an electrical enclosure.

5.2 Diagrama de fiação

Connect the device according to the following wiring diagram. Ensure all connections are tight and secure to prevent loose contacts and potential hazards. Always disconnect power before performing any wiring.

Wiring diagram for the GEYA GPS6-VAK device with a circuit breaker and load.

Image: A wiring diagram showing the connection of the GPS6-VAK device. The 'L' (Live) and 'N' (Neutral) inputs are connected to the power source, typically through a circuit breaker. The outputs from the device are then connected to the 'Load'.

  • Connect the incoming Live (L) and Neutral (N) wires to the respective input terminals of the device.
  • Connect the Live and Neutral wires from the device's output terminals to your electrical load.
  • It is recommended to install a circuit breaker upstream of the protection device for additional safety and circuit isolation.

6. Instruções de operação

6.1 Visor Digitalview

The device features a large-screen color digital display that shows real-time electrical parameters.

Close-up of the GEYA GPS6-VAK digital display showing voltage, current, and KWH readings.

Imagem: Uma imagem detalhada view of the GPS6-VAK's digital display. It shows the current voltage (e.g., 220V), current (e.g., 00.0A), and cumulative KWH (e.g., 000.0 KWH). The display also indicates the 'SET' button and navigation arrows for adjustments.

  • Volumetage Exibição: Mostra o volume em tempo realtage (por exemplo, 220V).
  • Exibição atual: Shows the real-time current (e.g., 00.0A). Note: The current value may not be displayed when below 1A.
  • KWH Display: Shows the cumulative energy consumption. Note: This value may not be displayed when below 0.01 KWH.

6.2 Parâmetros de configuração

Use the 'SET' button and arrow keys (Up/Down) to navigate through the menu and adjust parameters such as overvoltage limiar, subvoltage threshold, and reset time. Refer to the on-screen menu for specific navigation and adjustment steps.

  • Press the 'SET' button to enter the setting menu.
  • Use the Up/Down arrow buttons to select the parameter you wish to adjust.
  • Press 'SET' again to confirm your selection and enter the adjustment mode.
  • Use the Up/Down arrow buttons to change the value.
  • Press 'SET' to save the new value and exit the adjustment mode.
  • The device features an automatic reset function after voltage recovery, with a factory default of 30 seconds, adjustable from 2 to 900 seconds.

7. Manutenção

The GEYA GPS6-VAK device requires minimal maintenance. To ensure optimal performance and longevity:

  • Regularly inspect the device and its connections for any signs of damage, loose wiring, or overheating.
  • Keep the device clean and free from dust and moisture. Use a dry, soft cloth for cleaning.
  • Assegure-se de que haja ventilação adequada ao redor do dispositivo para evitar o acúmulo de calor.
  • Não tente abrir ou reparar o dispositivo por conta própria. Contate pessoal qualificado para obter assistência técnica.

8. Solução De Problemas

If you encounter issues with your GEYA GPS6-VAK device, consider the following basic troubleshooting steps:

  • Dispositivo não liga: Check the main power supply and all wiring connections. Ensure the input voltage está dentro da faixa de operação do dispositivo.
  • Sem potência de saída: The device may have tripped due to overvoltage, subvoltage, or overcurrent. Check the display for fault indicators. The device should automatically reset after the set delay once the voltage volta ao normal.
  • Leituras incorretas: Verify that the wiring is correct and secure. Ensure the device is properly calibrated (though typically factory calibrated).
  • Tropeços frequentes: Review seu conjunto sobrevolumetage e subvol.tage thresholds. They might be set too close to your normal operating voltage, causing nuisance tripping. Adjust the reset time if necessary.

If the problem persists after performing these steps, contact GEYA customer support or a qualified electrician.

9. Aplicação Exampos

The GEYA GPS6-VAK is suitable for a wide range of applications, providing essential voltage and current protection in various environments.

Image showing multi-scenario applications for the GEYA voltage protector, including school, dormitory, rental house, and apartment settings.

Image: The GPS6-VAK device is depicted in various application settings such as schools, dormitories, rental houses, and apartments, highlighting its versatility for both household and commercial use.

  • Uso residencial: Protecting household appliances and electronics from voltage flutuações.
  • Commercial Buildings: Ensuring stable power for office equipment and lighting systems.
  • Instituições de ensino: Safeguarding sensitive laboratory equipment and classroom electronics.
  • Rental Properties: Providing reliable power protection for tenants.

10. Garantia e Suporte

For warranty information, technical support, or service inquiries, please refer to the official GEYA webou entre em contato com seu revendedor autorizado. Guarde o comprovante de compra como prova de aquisição.

GEYA Official Website: Visit GEYA Store on Amazon

Ask a question about this manual