Watts 009M2 Reduced Pressure Zone Backflow Preventer (Model 0063010) Instruction Manual

For Models: 009M2, 009M2-QT

1. Introdução

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Informações importantes de segurança

3. Produto acabadoview e Componentes

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Configuração e instalação

  1. Verificação de pré-instalação:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Inspecione a unidade para verificar se há danos causados ​​pelo transporte.
    • Ensure all necessary tools and materials for installation are available.
  2. Preparação do local:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Conexão de tubulação:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Verificação pós-instalação:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Inspecione todas as conexões quanto a vazamentos.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Instruções de operação

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. Manutenção

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. Solução De Problemas

ProblemaPossível causaSolução
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
Sem fluxo de água ou com fluxo reduzido
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Certifique-se de que as válvulas de fechamento estejam totalmente abertas.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
Vazamentos de conexões
  • Improperly sealed threads
  • Juntas danificadas
  • Re-apply thread sealant and tighten connections.
  • Inspect and replace gaskets.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Especificações

Número do modelo0063010 (009M2)
Backflow Preventer TypeMontagem de Zona de Pressão Reduzida
Material do corpoBronze
Tamanho da conexão de entrada/saída2 polegadas (50 mm)
Inlet/Outlet Connection TypeFemale Threaded NPT
Pressão Máxima de Trabalho175 PSI (12.10 BAR)
Temperatura Máxima180°F (82°C)
Temperatura mínima33°F (0.5°C)
Tipo de proteçãoBackpressure and Backsiphonage
Dimensões do produto (C x L x A)22 x 10 x 8 polegadas
Peso do item27 libras
Lead Free StatusNO (For non-potable use only)

9. Garantia e Suporte

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts website. Please refer to these resources for the most current warranty terms and conditions.

For technical support, replacement parts, or further assistance, please contact Watts customer service or visit their official website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Oficial de Watts Website: www.watts.com

Documentos relacionados - 0063010

Préview Especificações de engenharia do conjunto da zona de pressão reduzida da série Watts LF909
Especificações técnicas completas para o conjunto de zona de pressão reduzida da série Watts LF909 (2 1/2" - 10"). Detalha características, operação, materiais, dimensões e capacidade deste dispositivo de prevenção de refluxo sem chumbo com sensor de inundação integrado.
Préview Série Watts 009, LF009, LFU009, SS009, U009: Manual de Instalação, Manutenção e Reparo
Este manual completo da Watts fornece orientações essenciais para a instalação, manutenção e reparo dos conjuntos de zona de pressão reduzida das séries 009, LF009, LFU009, SS009 e U009. Ele detalha avisos de segurança, procedimentos de instalação, inspeção, manutenção, solução de problemas e informações sobre a garantia desses dispositivos críticos de prevenção de refluxo.
Préview Watts Series 909, LF909, 909RPDA Reduced Pressure Zone Assemblies Installation, Maintenance, and Repair Manual
Comprehensive guide for the installation, maintenance, and repair of Watts Series 909, LF909, and 909RPDA Reduced Pressure Zone Assemblies, including safety warnings, installation guidelines, testing procedures, servicing instructions, troubleshooting, and warranty information.
Préview Conjuntos de Zona de Pressão Reduzida da Série LF909 da Watts - Especificações Técnicas
Especificações técnicas detalhadas dos conjuntos de zona de pressão reduzida da série LF909 da Watts, incluindo características, operação, dimensões, pesos e capacidade. Projetados para controle de interconexões de água potável.
Préview Watts Series 009, LF009, LFU009, SS009, U009 Reduced Pressure Zone Assemblies Installation, Maintenance, and Repair Manual
Comprehensive guide for the installation, maintenance, and repair of Watts Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies, covering safety, installation procedures, annual inspection, troubleshooting, and service. Includes details on flood sensor activation and connection kits.
Préview Watts Series LF009 Reduced Pressure Zone Assembly - Technical Specifications
Detailed engineering specifications for the Watts Series LF009 Reduced Pressure Zone Assembly, including features, materials, dimensions, pressure ratings, and performance data for sizes 1/4" to 3".