HT-Instruments COMBI 420

HT-Instruments Logo

Manual do Usuário do Testador Multifuncional HT-Instruments COMBI 420 VDE 0100

Model: COMBI 420

1. Introdução

This user manual provides comprehensive instructions for the safe and effective operation of the HT-Instruments COMBI 420 Multifunction VDE 0100 Tester. The COMBI 420 is an advanced and versatile instrument designed for quick and easy verification of electrical installations. It performs tests in accordance with VDE (EN61557) parts 2, 3, 4, 6, and 7, and includes single-phase network analysis capabilities. Please read this manual thoroughly before using the device to ensure proper functionality and user safety.

2. Informações de segurança

Aviso: Electrical testing can be hazardous. Always follow local safety regulations and procedures. Failure to do so may result in injury or damage to the equipment.

3. Produto acabadoview

The HT-Instruments COMBI 420 is a robust and user-friendly multifunction tester. It features a large, clear LCD screen with backlight and a graphical help menu for intuitive operation.

HT-Instruments COMBI 420 Multifunction Tester

Figure 3.1: HT-Instruments COMBI 420 Multifunction Tester. The device features a large LCD display, navigation buttons, and input terminals for various measurements.

3.1 Principais Características

3.2 Conteúdo da embalagem

The COMBI 420 package includes:

4. Configuração

4.1 Instalação da bateria

The COMBI 420 requires 6 AA alkaline batteries. These are typically included with the device. To install or replace batteries:

  1. Certifique-se de que o dispositivo esteja desligado.
  2. Localize o compartimento da bateria na parte traseira do dispositivo.
  3. Abra a tampa do compartimento.
  4. Insira 6 pilhas AA, observando a polaridade correta (+/-) indicada dentro do compartimento.
  5. Feche bem a tampa do compartimento da bateria.

4.2 Connecting Test Leads and Accessories

Connect the appropriate test leads and accessories to the input terminals on the COMBI 420 based on the measurement you intend to perform. Always ensure connections are secure.

5. Instruções de operação

5.1 Ligar/Desligar

Pressione o PODER button to turn the device on. The device will perform a self-test and display the main menu. To turn off, press and hold the PODER button, or allow the automatic shutdown feature to activate after a period of inactivity.

5.2 Navegação e Exibição

Use the directional buttons and the DIGITAR button to navigate through the menus and select functions. The large LCD screen displays measurement results, settings, and the graphical help menu. Press ESC / MENU to return to the previous menu or access the main menu. The AJUDA button provides on-screen assistance for current functions.

5.3 Funções de Medição

The COMBI 420 offers a wide range of measurement capabilities. Always refer to the on-screen help or specific sections of this manual for detailed connection diagrams and procedures for each test.

  1. Low-Ohm Measurement (Continuity):

    Measures resistance with a test current of >200 mA DC, compliant with VDE 0413 part 4 (EN 61557-4). Used to verify the continuity of protective conductors and equipotential bonding.

  2. Teste de isolamento:

    Performs insulation resistance measurements at 50, 100, 250, 500, or 1000 V DC, compliant with VDE 0413 part 2 (EN 61557-2). Essential for checking the integrity of insulation in electrical systems.

  3. FI (RCD) Test and Analysis:

    Comprehensive testing of Residual Current Devices (RCDs) according to VDE 0413 part 6 (EN 61557-6). Includes trip time, trip current, and contact voltage medições.

  4. Loop and Network Impedance Measurement:

    Measures loop impedance and network impedance, compliant with VDE 0413 part 3 (EN 61557-3). This is crucial for determining prospective fault current and ensuring proper circuit breaker operation.

  5. Short-Circuit Current Ik Display:

    Displays the calculated prospective short-circuit current (Ik) based on impedance measurements, as per VDE 0413 part 3 (EN 61557-3).

  6. Loop Resistance without RCD Tripping:

    Allows loop resistance measurement in circuits protected by RCDs without causing the RCD to trip, using a low test current.

  7. Rotating Field Direction Measurement:

    Determines the phase sequence (rotating field direction) in three-phase systems, compliant with VDE 0413 part 7 (EN 61557-7). This can be performed even with a single test probe.

  8. Power Measurement and Harmonic Analysis:

    Measures active, reactive, and apparent power, as well as power factor. Performs harmonic analysis of voltage and current up to the 49th harmonic and calculates Total Harmonic Distortion (THD) in percentage.

  9. External Probe Measurements:

    When connected, the device can display readings from external humidity, temperature, light (lux), and sound level probes.

5.4 Armazenamento e Transferência de Dados

The COMBI 420 has an internal memory capable of storing up to 600 measurement values. Use the SALVAR button to store current measurement results. Data can be transferred to a PC using the integrated optical USB interface and the provided Topview software.

6. Manutenção

6.1 Limpeza

Clean the device regularly with a soft, dry cloth. Do not use abrasive cleaners or solvents. Ensure no moisture enters the device.

6.2 Substituição da bateria

Replace batteries when the low battery indicator appears on the display. Refer to Section 4.1 for battery installation instructions. Always use new, high-quality AA alkaline batteries.

6.3 Calibração

For continued accuracy and compliance, periodic calibration by an authorized service center is recommended. The device is supplied with an ISO 9000 calibration protocol, indicating its initial calibration status.

7. Solução De Problemas

If you encounter issues with your COMBI 420, try the following basic troubleshooting steps:

For more complex issues, utilize the device's built-in graphical help menu or contact HT-Instruments technical support.

8. Especificações

RecursoEspecificação
Número do modeloCOMBI 420
FabricanteHT-Instruments
Dimensões do produto (C x L x A)24 x 17 x 8 cm (aproximadamente 9.45 x 6.69 x 3.15 polegadas)
Peso3 kg (aprox. 6.6 lbs)
Fonte de energiaBattery-Powered (6 AA batteries required, included)
Conformidade de segurançaIEC-1010-1, CAT III 415 V
Padrões de MediçãoVDE (EN61557) parts 2, 3, 4, 6, 7
Memória interna600 valores de medição
InterfaceUSB óptico
Componentes incluídosPrincipalview software, USB cable, storage bag, measurement cable with earthed plug, 3 safety test leads, 2 test probes, 3 crocodile clips, batteries, user manual, ISO 9000 calibration protocol

9. Garantia e Suporte

HT-Instruments products are manufactured to high quality standards. For specific warranty information, please refer to the documentation included with your purchase or visit the official HT-Instruments website. For technical support, service, or inquiries regarding calibration, please contact your local HT-Instruments distributor or customer service department.

Documentos relacionados - COMBI 420

Préview COMBI521 Multifunction Tester: Electrical Safety, Power Quality & EVSE Testing
Comprehensive technical specifications for the HT Instruments COMBI521 multifunction tester, detailing its capabilities for electrical installation safety tests, power quality analysis, and EVSE safety tests. Includes measurement functions, detailed technical data, general specifications, and compliance information.
Préview Manual do Usuário do HT Instruments PV-ISOTEST
Manual do usuário completo para o HT Instruments PV-ISOTEST, detalhando precauções de segurança, funções do instrumento, instruções de operação, especificações técnicas e solução de problemas para testes de isolamento fotovoltaico.
Préview HT Instruments M70 Handheld Insulation/Continuity Meter Specifications and Features
Detailed specifications, features, and reference standards for the HT Instruments M70 handheld insulation and continuity meter, capable of up to 1000VDC. Includes information on electrical tests, power, and operating conditions, along with services offered by EURO-INDEX.
Préview HT Instruments NEPTUNE Multifunction Professional Safety Multimeter Datasheet
Comprehensive datasheet for the HT Instruments NEPTUNE, a professional safety multimeter. Details electrical specifications, features, power supply, environmental conditions, and compliance information.
Préview HT Instruments HT7 Digital Voltage Manual do usuário do testador
Comprehensive user manual for the HT Instruments HT7 digital voltage tester, covering safety instructions, operating procedures, technical specifications, and maintenance for safe and effective use.
Préview HT Instruments MACROTESTG3 - Testador de Segurança Profissional para Instalações - Especificações e Recursos
Especificações técnicas detalhadas, parâmetros elétricos, capacidades de teste de DR (Disjuntor Diferencial Residual), impedância de loop, resistência de isolamento, volumetage, medições de corrente, fator de potência e harmônicos do testador de segurança de instalação profissional MACROTESTG3 da HT Instruments.