Watts WATTS - 118946

Watts 0342691 30 PSI Pressure Relief Valve User Manual

Model: WATTS - 118946

Introdução

This manual provides essential information for the proper installation, operation, and maintenance of the Watts Series 335 ASME rated Boiler Pressure Relief Valve. This valve is designed for hydronic systems, specifically for boilers up to 510,000 BTU at a 30 PSI (2.11 bar) set point. Its compact, all-bronze construction makes it suitable for various OEM boiler applications.

Watts 30 PSI Pressure Relief Valve, front view

Figura 1: Frente view of the Watts 30 PSI Pressure Relief Valve, showing the bronze body and the pressure relief lever.

Informações de segurança

Always follow local codes and regulations during installation and maintenance. Ensure the system is depressurized and cooled before attempting any work on the valve. Wear appropriate personal protective equipment (PPE).

Configuração e instalação

The Watts 0342691 Pressure Relief Valve is designed for straightforward installation. It features a 3/4-inch female threaded inlet and a 3/4-inch FNPT outlet.

  1. Preparação: Ensure the boiler system is completely shut down, depressurized, and cooled. Drain any water from the system if necessary.
  2. Remova a válvula antiga (se aplicável): Carefully unthread the existing pressure relief valve from the boiler.
  3. Aplique selante de rosca: Apply an appropriate thread sealant (e.g., PTFE tape or pipe dope) to the male threads of the new Watts valve.
  4. Instalar nova válvula: Thread the new valve into the boiler's pressure relief valve port. Tighten securely with a wrench, ensuring not to overtighten.
  5. Connect Discharge Piping: Attach appropriate discharge piping to the valve's outlet. This piping must be sized correctly and routed to a safe discharge point, preventing scalding or property damage.
  6. Repressurização do sistema: Slowly re-pressurize the boiler system and check for any leaks around the newly installed valve and connections.
Watts 30 PSI Pressure Relief Valve, side view

Figura 2: Lateral view of the Watts 30 PSI Pressure Relief Valve, showing the compact design and connection points.

Princípios operacionais

The Watts 0342691 is an automatic pressure relief valve designed to protect hydronic heating systems from over-pressurization. It is factory-set to open at 30 PSI (Pounds per Square Inch). When the system pressure exceeds this set point, the valve will automatically open, discharging water to relieve the excess pressure and prevent damage to the boiler or system components. Once the pressure drops below the set point, the valve will automatically close.

The valve also features a manual test lever. This lever allows for periodic manual testing of the valve's operation. When the lever is lifted, the valve will open, discharging water. It is important to exercise caution when using the test lever, as hot water may be discharged.

Manutenção

Regular maintenance ensures the longevity and proper function of your pressure relief valve.

Solução de problemas

ProblemaPossível causaSolução
Valve constantly dripping or leaking
  • Pressão do sistema muito alta
  • Sediment or debris under the seat
  • Worn or damaged internal components
  • Improper installation (e.g., insufficient thread sealant)
  • Check system pressure; ensure it is below 30 PSI.
  • Briefly lift the test lever to flush out debris.
  • If leaking persists, the valve may need replacement.
  • Re-install with proper thread sealant if leak is from threads.
Valve does not open when pressure is high
  • Valve seized due to corrosion or lack of use
  • Incorrect valve installed (wrong pressure setting)
  • Attempt to operate the manual test lever.
  • If it remains seized, the valve must be replaced immediately to prevent system damage.
  • Verify the valve's pressure rating matches system requirements.

Especificações

Watts 30 PSI Pressure Relief Valve with dimensions shown against a hand

Figure 3: The Watts 30 PSI Pressure Relief Valve demonstrating its compact size, approximately 2.9 inches (7 cm) in height.

AtributoValor
Número do modeloWATTS - 118946
MaterialBronze
Tamanho da conexão de entrada3/4 polegadas
Tipo de conexão de entradaFemale Threaded
Tamanho da conexão de saída3/4 polegadas
Tipo de conexão de saídaFNPT
Pressão máxima de operação30 PSI (2.11 bar)
Classificação BTUAté 510,000 BTU
Número de portas2
Dimensões (C x L x A)3 x 2.3 x 1.8 polegadas
Peso0.01 ounces (Note: This seems unusually low, likely a data entry error in source. Actual weight for such a valve would be higher.)
Especificação AtendidaASME Section IV

Informações de garantia

Specific warranty details for this product are not provided in this manual. Please refer to the manufacturer's official website or contact Watts customer service for current warranty terms and conditions.

Suporte e Contato

For technical assistance, replacement parts, or further information, please contact Watts customer support or visit their official website.

Oficial de Watts Website: www.watts.com

Watts Store on Amazon: Visit the Watts Store

Documentos relacionados - WATTS - 118946

Préview Watts LF1L, LF1XL, LF10L, LF100XL Temperature and Pressure Relief Valves - Technical Specification
Detailed technical specification for Watts Series LF1L, LF1XL, LF10L, and LF100XL Lead Free Temperature and Pressure Relief Valves, including features, specifications, dimensions, and safety warnings.
Préview Válvula redutora de pressão Watts com recurso de retenção hidráulica - Série em aço inoxidável
Fim técnicoview Este documento descreve detalhadamente a válvula de retenção e redução de pressão combinada Watts ACV, seu funcionamento, diretrizes de instalação e uma lista de modelos de válvulas de controle relacionadas.
Préview Installation Instructions for Watts Sensor Control Monitor Connection Kit
Comprehensive installation guide for the Watts Sensor Control Monitor Connection Kit, detailing setup, wiring, configuration, and integration with BAS and Nexa platforms. Includes safety information and product specifications.
Préview Watts W-M115 ACV Pressure Reducing Valve: Specification & Installation Guide
Comprehensive guide detailing the specifications, dimensions, flow rates, operating principles, installation, and start-up procedures for the Watts W-M115 ACV Pressure Reducing Valve. Essential information for industrial and commercial applications.
Préview Guia de Instalação do Kit de Conexão para Retrofit do Sensor de Inundação Watts BMS
Este guia fornece instruções detalhadas de instalação para o Kit de Conexão de Retrofit do Sensor de Inundação Watts BMS (Modelo IS-RFK-FS-ReliefValve-BMS). Ele abrange os componentes do kit, requisitos, preparação, etapas de instalação, diagramas de fiação e informações sobre a garantia para o monitoramento das linhas de descarga da válvula de alívio.
Préview Especificações Técnicas Séries Watts SL100XL, L100XL, LL100XL, LLL100XL
Especificações técnicas completas para as sopas de descarga de temperatura e pressão ao longo das séries Watts SL100XL, L100XL, LL100XL e LLL100XL. Detalhes sobre as características, dimensões, instalação e segurança para a água.