VOLTCRAFT VC40

VOLTCRAFT VC40 Socket Tester

Model: VC40 | CAT II 300 V

Introdução

The VOLTCRAFT VC40 is a compact and reliable socket tester designed to quickly verify the correct wiring of electrical sockets and test Residual Current Devices (RCDs) with a 30 mA trip current. This device provides visual and audible indications for various wiring conditions, ensuring electrical safety in your installations. It is rated for CAT II 300 V applications.

Informações de segurança

Please read and understand all safety instructions before using this device.

Produto acimaview

The VOLTCRAFT VC40 features an automatic testing process, finger contacts for protective conductor and RCD tests, and provides clear visual and audible signals for test results.

VOLTCRAFT VC40 Socket Tester (Angled View)

Imagem: Angulada view of the VOLTCRAFT VC40 Socket Tester, showing its compact design and plug. This image illustrates the overall appearance of the device.

VOLTCRAFT VC40 Socket Tester (Front View with Indicators)

Imagem: Frente view of the VOLTCRAFT VC40 Socket Tester, clearly displaying the LED indicators and their corresponding wiring conditions and test functions. This is essential for interpreting test results.

VOLTCRAFT VC40 Socket Tester (Rear View)

Imagem: Traseira view of the VOLTCRAFT VC40 Socket Tester, showing the plug pins and the speaker grille for audible signals.

Configurar

The VOLTCRAFT VC40 is designed for immediate use. No assembly or battery installation is required as it draws power directly from the socket being tested.

  1. Certifique-se de que o testador de tomadas esteja limpo e sem danos.
  2. Verify that the electrical circuit you intend to test is live and within the device's specified voltage range (230V 50Hz).

Instruções de operação

1. Wiring Check

To check the wiring of a socket:

  1. Plug the VOLTCRAFT VC40 directly into the socket you wish to test.
  2. The device will automatically perform a wiring check. Observe the LED indicators and listen for the audible signal.
  3. Refer to the 'Interpreting Indicators' section below to understand the test result.

2. Teste do DR (Dispositivo de Corrente Residual)

To test an RCD (30 mA trip current):

  1. First, perform a wiring check as described above to ensure the socket is correctly wired.
  2. With the VC40 plugged into the socket, place your fingers on the two metal contact points labeled for RCD test. This initiates the RCD trip test.
  3. The RCD should trip, cutting power to the circuit. The VC40's indicators should go off.
  4. If the RCD does not trip, refer to the 'Troubleshooting' section.
  5. Reset the RCD at your consumer unit/fuse box after the test.

3. Interpreting Indicators

The VC40 uses a combination of green and red LEDs, along with an audible tone, to indicate the wiring status. The labels on the device correspond to the conditions detected.

Padrão indicadorSinal AudívelSignificado
All Green LEDs (TONE ON CORRECT)Tom ContínuoFiação correta: Live, Neutral, and Earth are correctly connected.
Specific Red/Green LED combination (PULSE MISSING EARTH)Pulsing ToneMissing Earth: The protective earth conductor is not connected or faulty.
Specific Red/Green LED combination (PULSE LIVE EARTH REVERSE)Pulsing ToneLive Earth Reverse: The live and earth conductors are reversed. This is a dangerous condition.
Specific Red/Green LED combination (PULSE LIVE NEUTRAL REVERSE)Pulsing ToneLive Neutral Reverse: The live and neutral conductors are reversed.
All Red LEDs (FAULT >50V EARTH VOLTS)No specific tone indicated, but implies fault.Fault >50V Earth Volts: Indica um volume perigosotage present on the earth line.
Specific Red/Green LED combination (FAULT NO TRIP RCD 30mA)No specific tone indicated, but implies fault.RCD Fault (No Trip): The RCD did not trip during the test, indicating a potential fault with the RCD itself.

Note: The exact LED patterns for each fault are indicated on the device itself. Always refer to the labels on the VC40 for precise interpretation.

Manutenção

The VOLTCRAFT VC40 requires minimal maintenance.

Solução de problemas

If you encounter issues with your VOLTCRAFT VC40, refer to the following common problems and solutions:

Especificações

RecursoEspecificação
Número do modeloVC40
MarcaVOLTCRAFT
Volumetage AvaliaçãoCATII 300V
Vol operacionaltage230 Volts (CA)
Freqüência50 Hz
Corrente de teste do RCD30 mA
Fonte de energiaManual operation (draws power from socket)
Dimensões (C x L x A)8.3 x 8.3 x 7.7 cm
Peso80 gramas
Temperatura Máx. de Operação85 graus Celsius

Garantia e Suporte

VOLTCRAFT products are built to high standards. This product typically comes with a manufacturer's warranty. Please refer to your purchase documentation for specific warranty terms and duration. Spare parts availability is generally 1 year from the date of purchase.

For technical support, troubleshooting assistance, or warranty claims, please contact VOLTCRAFT customer service or your retailer. Keep your purchase receipt as proof of purchase.

Documentos relacionados - VC40

Préview VOLTCRAFT GT-6000 v2: Bedienungsanleitung für den Gerätetester
Umfassende Bedienungsanleitung für den VOLTCRAFT GT-6000 v2 Gerätetester. Erfahren Sie mehr über Funktionen, Sicherheitshinweise, Messungen und technische Daten.
Préview Testador VOLTCRAFT PM-42 USB-A 2.0 com a última leitura de dados
Um guia de instruções confiável para o testador VOLTCRAFT PM-42 USB-A 2.0 com o último. Este dispositivo perdeu a extensão, a potência, a capacidade e a energia do dispositivo USB e o protocolo de conexão unterstützt. Enthält Sicherheitshinweise e dados técnicos.
Préview VOLTCRAFT VC-1320 AC TRMS Leakage Clamp Meter - Technical Datasheet
Detailed technical specifications and features for the VOLTCRAFT VC-1320 AC TRMS Leakage Clamp Meter, including measurement ranges, accuracy, safety ratings, and package contents.
Préview Voltcraft EL-1000/EL-2000 Series Programmable DC Electronic Load User Manual
Comprehensive user manual for the Voltcraft EL-1000 and EL-2000 series programmable DC electronic loads, covering features, operation, specifications, and safety information.
Préview VOLTCRAFT VC-BT300PRO OBDII + Testador de bateria Bedienungsanleitung
Um guia de instruções confiável para o VOLTCRAFT VC-BT300PRO, um método de diagnóstico para OBD-II e testes de bateria. Funções básicas, segurança e dados técnicos.
Préview VOLTCRAFT VBM-50 Schwingungsmessgerät Bedienungsanleitung
Estas informações detalhadas são fornecidas pelo VOLTCRAFT VBM-50 Schwingungsmessgerät (Número do artigo 3394395), funções específicas do seiner, instruções de segurança, especificações técnicas e instruções para o dispositivo mecânico superior.